Description
30 hp (22 kW) high performance variable frequency drive, three phase 208V, 440V, 460V for selection, manufacturer direct sale.
Specification:
| Basics | Model | GK3000-4T0220G/ GK3000-2T0220G |
| Capacity | 30 hp (22 kW) | |
| Shipping weight | 8 kg | |
| Dimension | 330*200*200 mm for GK3000-4T0220G/ 555*310*260 for GK3000-2T0220G | |
| I/O Feature | Rated current | 45A at 380V ~ 480V, 91A at 220V ~ 240V |
| Input voltage | 3 phase 208V /440V /460V AC ±15% (Optional) | |
| Input frequency | 50Hz/ 60Hz | |
| Output voltage | 3 phase AC 0~input voltage | |
| Output frequency | 0Hz~1000Hz | |
| Over load capacity | 150% of rated current for 1 minute, 180% of rated current for 3 seconds | |
| Control Feature | Control mode | V/F control; Sensorless vector control; |
| Communication | RS485 | |
| Speed regulation | 1:100 | |
| Start torque | 150% of rating torque at 1 Hz | |
| Speed control accuracy | ≤±0.5% of rating synchronous speed | |
| Frequency precision | Digital setting: max frequency x± 0.01%; Analog setting: max frequency x± 0.2% |
|
| Frequency resolution | Analog setting: 0.1% of max frequency; Digital setting: 0.01Hz |
|
| Torque boost | Automatic torque boost, manual torque boost 0.1%~30.0% | |
| Interior PID controller | Be convenient to make closed-loop system | |
| Automatic energy save running | Optimize V/F curve automatically based on the load to realize power save running | |
| Automatic voltage regulation (AVR) | Can keep constant output voltage when power source voltage varies. | |
| Automatic current limiting | Limit running current automatically to avoid frequent over-current which will cause trip | |
| Environment | Enclosure rating | IP 20 |
| Temperature | –10℃~ +40℃; VFD will be derated if ambient temperature exceed 40℃; each rise 1℃, the debate will be 5% | |
| Humidity | 5%-95%, without condensation | |
| Altitude | ≤1000m; VFD will be derated if above 1000m | |
| Impingement and oscillation | Normal running:<5.9m/s2 (0.6g); Transportation:<15m/s2 (1.5g) | |
| Store environment | –20℃~ +60℃; no dust, no corrosive gas, no direct sunlight |
Note: ATO VFD Cannot be used as a power source, it Can only be directly connected to an induction motor to control the motor speed.
Tips: Variable frequency drive overheated
Overheating is also a relatively common failure of VFD, which is mainly caused by high environment temperature, fan locked-rotor, poor temperature sensor performance or motor overheating.
For example, a 30 hp VFD displays “OH” after running for about half an hour.
Analysis and maintenance: Because the failure happens after a period of running, so the temperature sensor is not likely to be broken. Maybe VFD temperature is truly high. After power on, find the fan is slowly rotating, and there is a lot of cotton inside the shield (VFD is used in the textile industry). After cleaning the fan, VFD runs well, and doesn’t display the failure for hours of running.