Description
250 hp AC motor soft starter, 185 kW three phase 220v, 380v, 480v, 690v starter.
| Model | GS2-185 (220v, 240v), GS3-185 (380v, 400v, 415v), GS4-185 (460v, 480v), GS6-185 (550v, 690v). | |
| Capacity | 250 hp (185 kw) | |
| Current | 370 amps at 380v/480v, 710 amps at 220v | |
| Weight | 21 kgs | |
| Dimension | 525*257*194 mm | |
| Input | Voltage | Three-phase 230v, 440v, 480v, 660v AC |
| Frequency | 50Hz/ 60Hz | |
| Adaptive Motor | Squirrel-cage three-phase asynchronous motor | |
| Starting Times | It is recommended not to exceed 20 times per hour. | |
| 485 Communication | DB9 interface, male plug, ① is RS485+, ⑥ is RS485- | |
| Control Mode |
|
|
| Start Mode |
|
|
| Stop Mode |
|
|
| Protective Function |
|
|
| Ambient | Place to be used | Indoor location with good ventilation free from corrosive gas and conductive dust. |
| Altitude | Below 1000M. It has to increase the soft starter rate power when the altitude is more than 1000M. | |
| Temperature | -30 +55 oC | |
| Humidity | 90%RH without dew condensation. | |
| Vibration | <0.5G | |
| Structure | Enclosure | IP 20 |
| Cooling | Natural wind cooling. |
Details
Tips: Soft starter starting fault and its handling method part 1
- In the start-up process, the soft starter has the occasional jump air switch phenomenon. The causes for the malfunction are:
Long delay setting value of air switch is too small or air switch selection does not match with the motor. (Air switch parameters are moderately enlarged or the air switch is reselected.)
The starting voltage parameter is set too high or the starting time is too long. (The initial voltage is appropriately adjusted or the starting time is appropriately shortened according to the load condition.)
In the process of starting, because fluctuations in the grid voltage are relatively large, it is easy to cause the error commands issued by the soft starter and an early bypass phenomenon. (It is recommended that users do not start high-power motor at the same time.)
Start at full load. (Minimize the load when starting.) - The soft starter reports fault when starting, the soft starter does not work, the motor does not respond. The causes of the failure may be:
Default phase of motor. (Check motor and peripheral circuit.)
Short circuit of SCR of main elements in soft starter. (Check whether the motor and the grid voltage are abnormal Connect with the manufacturers to replace the SCR.)
Filter board breaks down short circuit. (Replace the filter board.) - In the starting process, the current is instable and the current is too large. The reasons may be:
Ammeter indication is not accurate or does not match the transformer. (Replace the new ammeter.)
Grid voltage has instability, fluctuations are relatively large, causing the malfunction of the soft starter. (Connect with the manufacturers to replace the control panel.)
Soft starter parameter setting is unreasonable. (Retune the parameters.) - The soft starter has repeated start. The causes for the malfunction are:
During the starting process, the external protective elements move, the contactor cannot be closed, resulting in repeated starting of the soft starter. (Check peripheral components and lines.)